Página 1 - INSTALLATION

INSTALLATIONMANUALCross Platform ControlPart # ELK-M1EZ8A member of the M1 FamilySpecifications, Installation and ProgrammingM1 includes the SIA CP-01

Página 2 - Introduction

M1EZ8 Installation and ProgrammingPage 10AC Failure, Low Battery, and Automatic Low Voltage ShutdownDuring an AC power failure the battery automatical

Página 3 - Table of Contents

M1EZ8 Installation and ProgrammingPage 11Data Bus E.O.L. Termination - VERY IMPORTANT!The control features a true RS-485 “differential” data bus opera

Página 4

M1EZ8 Installation and ProgrammingPage 12Setting the Data Bus Address and Enrolling Device(s) into the SystemKeypads and expander devices communicate

Página 5 - Wiring & Hookup Diagram

M1EZ8 Installation and ProgrammingPage 132.1 IntroductionThe control has factory default programming which make it easy to bench test prior to install

Página 6 - Intentionally Left Blank

M1EZ8 Installation and ProgrammingPage 142.5 Keypad OverviewReady Light - ON when all burglar zones are secure and the system is OK to arm. If OFF, o

Página 7 - 1.1 Planning the Installation

M1EZ8 Installation and ProgrammingPage 15Access to menus 1 to 5 can be restricted via programming to only Users that have “User Code Option 8” set. M

Página 8 - 1.4 Control Wiring

M1EZ8 Installation and ProgrammingPage 163-Walk Test Area r < Area? Name >4-View History rLog6-Change rUser CodesRequires Master orInstaller Co

Página 9 - 16V XFMR

M1EZ8 Installation and ProgrammingPage 17To perform system tests press the right arrow key. Then press the up or down arrow keys toselect one of the t

Página 10 - Earth Grounding

M1EZ8 Installation and ProgrammingPage 189-Installation rProgramming (0)RequiresInstallerCodeFrom this menu you may press the RIGHT arrow to enter Ins

Página 11 - Terminate

M1EZ8 Installation and ProgrammingPage 193.1 IntroductionThe Security functionality of the Control can be programmed either from an ELK-M1KP LCD Keypa

Página 12

M1EZ8 Installation and ProgrammingPage 2IntroductionLIMITATIONThis Control is designed to warn against unauthorized entry and other situations. Howeve

Página 13 - 2.2 Powering Up (One Keypad)

M1EZ8 Installation and ProgrammingPage 203.5 Communicator Setup ChecklistThe Communicator (Dialer) can dial up to 8 phone numbers plus RP. Digital re

Página 14 - 2.5 Keypad Overview

M1EZ8 Installation and ProgrammingPage 21ELK-EZ8 QUICK REFERENCE - MENU PROGRAMMINGMenu 01 Menu 04 Menu 06 Menu 07 Menu 08 Menu 10 Menu 13Bus Mod Enr

Página 15 - Keypad Menus

M1EZ8 Installation and ProgrammingPage 22Menu 01 - Bus Module Enrollment01-Bus ModuleEnrollment rBus Module Enroll Description of OptionEnrollingBus M

Página 16

M1EZ8 Installation and ProgrammingPage 23001 09:=No rDuress001: Selb PrgrUser 1001 01:12345678 rCode used inArea001 02:=Yes rArm with Code001 03:=Yes

Página 17

M1EZ8 Installation and ProgrammingPage 24A1: Selb PrgrArea 1A1 01:=060 rExit Delay1 TimeA1 02:=030 rEntry Delay1TimeA1 03:=060 rExit Delay2 TimeA1 04:

Página 18 - Installer

M1EZ8 Installation and ProgrammingPage 25A1 11:=No rStayInstantScrA1 12:=Yes rNight ScrollA1 13:=No rNightInstantScrA1 14:=No rStayChgIfArmedIf Yes, a

Página 19 - 3.4 Area Partitioning

M1EZ8 Installation and ProgrammingPage 26KP01 03:=No rSilent on ExitKP01 04:=No rSilent on ChimeKP01 05:=No rGo dark in 60secKP01 06:=Yes rShow Date &

Página 20 - Enter Valid Pin

M1EZ8 Installation and ProgrammingPage 27Menu 04 - Keypad Definitions (continued)Keypad Definitions Description of OptionKP01 10:F1 Key rDefinitionsF

Página 21

M1EZ8 Installation and ProgrammingPage 28ZN001: Selb PrgrZone 001ZN001 01:Def=01 rBurg Entry/Exit1Menu 05 - Zone Definitions05-Zone rDefinitionsZone D

Página 22

M1EZ8 Installation and ProgrammingPage 29ZN001 02:Type=0r0=EOL SupervisedZN001 03:Area=1 r[Area Name]Refers to the wiring configuration for zones. B

Página 23 - Menu 02 - User Code Options

M1EZ8 Installation and ProgrammingPage 3Table of ContentsSpecifications, Features, and Benefits ...

Página 24 - Menu 03 - Area Definitions

M1EZ8 Installation and ProgrammingPage 30ZN001 13: =No rIn CrossZonePoolMenu 05 - Zone Definitions (continued)Zone Definitions Description of OptionDi

Página 25

M1EZ8 Installation and ProgrammingPage 31CT01:=00600 secrBurgDurationCT02:=00000 secrFireDurationMenu 06 - Alarm Duration Timers06-Alarm Cutoff rTimer

Página 26 - Menu 04 - Keypad Definitions

M1EZ8 Installation and ProgrammingPage 32G01:=G02: =Yes r12Hr Time DispG03: =No rDD/MM Date DispMenu 07 - Global System DefinitionsPress RIGHT arrow k

Página 27

M1EZ8 Installation and ProgrammingPage 33G14: =No Out1&2rChg YelpToBuzzerG15 - G25Menu 07 - Global System Definitions (continued)Global Sys Defin

Página 28 - Menu 05 - Zone Definitions

M1EZ8 Installation and ProgrammingPage 34Menu 07 - Global System Definitions (continued)Global Sys Definitions Description of Option† Output 2 can be

Página 29

M1EZ8 Installation and ProgrammingPage 35Menu 07 - Global System Definitions (continued)† This option sets the control to transmit automation task st

Página 30

M1EZ8 Installation and ProgrammingPage 36T1: Selb Prgr[Name for Tel#1]T1: 02: = 0 r0=Always ReportMenu 08 - Telephone Account Setup08-Telephone rAccou

Página 31

M1EZ8 Installation and ProgrammingPage 37T1: 12:=000000rAcct # for Area8T1: 13:=Yes RptrAreaAlms,RestUnbpT1: 14:=No RptrBypassesTelephone Acct Setup D

Página 32 - NOTE: The Cross Zone

M1EZ8 Installation and ProgrammingPage 38AR1: Selb PrgrReportCodesArea1AR1 01:000=Sec rDialer Delay TimeAR1 02:Code= 00rAlm Abort CodeMenu 09 - Area R

Página 33

M1EZ8 Installation and ProgrammingPage 39Area Report Codes Description of OptionDuress code will be reported if the area is armed or disarmed by a val

Página 34

M1EZ8 Installation and ProgrammingPage 4† Not evaluated by UL †† Not for use in UL Listed SystemsGeneral:• Large zone capacity: 8 on-board zones ex

Página 35 - † Not evaluated by UL

M1EZ8 Installation and ProgrammingPage 40Z001: Selb Prgr[Name of Zone]Z001:A=00 R=00 rByp=00 Tbl=00Menu 10 - Zone Reporting Codes10-Zone ReportngCode

Página 36

M1EZ8 Installation and ProgrammingPage 41Menu 11 - Keypad F-Key Reporting Codes11-Keypad F-KeyrReporting CodesPress RIGHT arrow key to select this men

Página 37

M1EZ8 Installation and ProgrammingPage 42SR01: 015=AC FailRpt Delay - MinrSR02: T=00 R=00 rAC Fail CodesSR03: 00 = AutorTest CodeMenu 12 - Sys Report

Página 38

M1EZ8 Installation and ProgrammingPage 43SR14: T=00 R=00 rPhone Line FaultSR15: T=00 R=00 rOutput 2 TroubleSR13: 00= Up/ rDownload EndLow Battery T (T

Página 39

M1EZ8 Installation and ProgrammingPage 44UR001: Selb Prgr[Name of User]UR001:O=00 C=00r[Name of User]Menu 13 - User Report Codes13-User ReportCodes rU

Página 40

M1EZ8 Installation and ProgrammingPage 45Menu 14 - Wireless DefinitionsWirelessDefinitions DescriptionThe Wireless Definitions menu is broken into fou

Página 41

M1EZ8 Installation and ProgrammingPage 46WZnxxx:Selr PrgrWireless ZoneWZnxxx 01:=No rEnable TransmitrWZnxxx02:=0 rSupervision TypeWZnxxx

Página 42

M1EZ8 Installation and ProgrammingPage 474.1 ELK-RP SoftwareELK-RP (RP) is a Windows based software package that is compatible with Windows 98and lat

Página 43

M1EZ8 Installation and ProgrammingPage 484.1.2 Check for ConflictsDuring the connect and disconnect process RP performs an automatic check of the data

Página 44 - Menu 13 - User Report Codes

M1EZ8 Installation and ProgrammingPage 494.3 Automation Rules and AttributesThe RP Automation Programming software offers powerful, easy to setup and

Página 45 - SWITCHES TO OFF!

M1EZ8 Installation and ProgrammingPage 5Wiring & Hookup Diagram-STATUSLINE SEIZEN.C.N.O.2200OhmEOLN.C.N.O.Zone82200OhmEOLPOWERData Bus-See Note in

Página 46

M1EZ8 Installation and ProgrammingPage 50† LIGHTING - The control can handle up to 256 Light (or appliance) devices. Each is assigned to one of 25

Página 47 - 4.1 ELK-RP Software

M1EZ8 Installation and ProgrammingPage 51CUSTOM SETTINGS - These are 20 memory locations which may be assigned a 12 character description, a function

Página 48 - 4.1.2 Check for Conflicts

M1EZ8 Installation and ProgrammingPage 52TEXTS - This section allows custom text messages to be constructed and formatted. These messages can be tran

Página 49

M1EZ8 Installation and ProgrammingPage 53RULES - This section essentially brings all the power of the control’s automation and its features together.

Página 50

M1EZ8 Installation and ProgrammingPage 54AND - The second and optional element of a rule is a qualifier. Rules can have one or more qualifiers OR non

Página 51

M1EZ8 Installation and ProgrammingPage 55Examples of Rules - Shown below are a series of rules that should help illustrate the power and results that

Página 52

M1EZ8 Installation and ProgrammingPage 560000 = No Event N0001 = Burg Entry/Exit 10002 = Burg Entry/Exit 20003 = Burg Perimeter Instant0004 = Burglar

Página 53

M1EZ8 Installation and ProgrammingPage 57“Reset” AttributeThe letter(s) displayed in Reset column indicate what condition(s) it takes toclear an event

Página 54

M1EZ8 Installation and ProgrammingPage 58Appendix B & C - Unused [Intentionally left blank]

Página 55

M1EZ8 Installation and ProgrammingPage 59[Intentionally left blank]

Página 56 - Appendix A - Event Codes

M1EZ8 Installation and ProgrammingPage 6Intentionally Left Blank

Página 57

M1EZ8 Installation and ProgrammingPage 60Appendix D - Two Way “Listen-in/Talk” Interface† Not evaluated by UL†Using a Two Way Interface board (ELK-E

Página 58 - [Intentionally left blank]

M1EZ8 Installation and ProgrammingPage 61This control has been self-verified to be compliant with the SIA CP-01 Control Panel Standard - Features for

Página 59

M1EZ8 Installation and ProgrammingPage 62Appendix F - Unused[Intentionally left blank]

Página 60 - Dialer Activated (Alarm)

M1EZ8 Installation and ProgrammingPage 63Appendix F - Unused[Intentionally left blank]

Página 61

M1EZ8 Installation and ProgrammingPage 64† Not evaluated by UL[Intentionally left blank]Appendix F - Unused

Página 62 - Appendix F - Unused

M1EZ8 Installation and ProgrammingPage 65M1KP KEYPAD ON-BOARD TEMPERATURE SENSOR †The ELK-M1KP Keypad has an on-board temperature sensor. (NOTE: The

Página 63

M1 LIMITED WARRANTYThe ELK-M1EZ8 and its associated component products are warranted by Elk Products, Inc. (“Manufacturer”) against defectsin material

Página 64

IndexAAlarm Abort 38Alarm Cutoff Timers 31Anti-Takeover 19Area Partitioning 19Area Reporting Codes 38, 39Auto Stay Option 25Automation control f

Página 65

www.elkproducts.comPrinted in USA

Página 66

M1EZ8 Installation and ProgrammingPage 71.1 Planning the InstallationThe first step in any multi-zone security system installation is planning the job

Página 67

M1EZ8 Installation and ProgrammingPage 81.4 Control WiringZone Inputs (1 thru 8 on main board, 17 thru 208 via expanders)Zones Z1 thru Z8 are on the m

Página 68 - Printed in USA

M1EZ8 Installation and ProgrammingPage 9Two-Wire Smoke Zone (Zone 8)To enable use of two-wire smoke detectors position Jumper JP1 to the 2 wire smoke